Numerical analysis by the linear viscoelastic method to determine the strength of seismic poundings between adjacent reinforced concrete buildings

Read Article

Date of Conference

July 18-22, 2022

Published In

"Education, Research and Leadership in Post-pandemic Engineering: Resilient, Inclusive and Sustainable Actions"

Location of Conference

Boca Raton

Authors

Orihuela, Junior

Huaraya, Katerine

Rojas, Alessandro

Abstract

Seismic excitation, in the presence of insufficient spacing between buildings, can cause damage to structures by external shocks from nearby buildings, due to the inertia force of seismic movements. In the present work, the analysis of three different buildings in their structural configuration and floor number is carried out to later quantify the force of mutual impact, generated by the seismic inertia forces. Linear History Time Analysis (ATHL) is performed in the direction of pounding analysis (East-West) obtaining the structural dynamic responses. The calculated impact force corresponds to the Interaction of said buildings. The results obtained show that a five-level building presents impact forces of 8.20 tf, 11.40 tf, 7.34 tf, 6.43 tf and 5.22 tf. This suggests approximately 24% of the basal shear.