In English:
The results of the experimental evaluation conducted to a solid state cooler of the liquid-gas type, are presented in
this paper. The intent is to install it at the condenser outlet to subcool the refrigerant in a vapor compression
refrigeration system of one ton of capacity. Experimental results show that the solid state cooler is capable of
providing a subcooling of 8 ° C to the refrigerant, leading to an increased cooling effect of the refrigeration
system. However, when considering the high electric power consumption of the solid state cooler this would
cause a decrease in the coefficiente of performance, COP, of the refrigeration system. Therefore, at the moment
its application is limited to systems that need to operate with a maximum value of the COP regardless of the
increment of ambient temperature.
In Spanish:
En este trabajo se presentan los resultados de la evaluación experimental que se realizó a un enfriador de estado
sólido del tipo líquido-gas. La intención es instalarlo a la salida del condensador para subenfriar el refrigerante en
un sistema de refrigeración por compresión de vapor con capacidad de una tonelada de refrigeración. Los
resultados experimentales muestran que el enfriador de estado sólido es capaz de proporcionar un subenfriamiento
del refrigerante de hasta 8 ºC, lo que conduce a un incremento del efecto refrigerante del sistema de refrigeración.
Sin embargo, al considerar el alto consumo de energía eléctrica del enfriador de estado sólido esto provoca una
disminución del coeficiente de operación, COP, del sistema de refrigeración. Por lo tanto, por el momento su
aplicación queda limitada a sistemas que necesiten operar con un valor máximo del COP independientemente del
aumento de la temperatura ambiente.
|